7.
Dismantling
7.1
Dismantling the DC-DC module
Connection cables carry life threatening voltage!
Ø
Fully discharge battery.
Ø
If the battery cannot be discharged: open separators on the
battery.
Ø
Disconnect the connection cables to the DC link voltage.
Ø
Maintain discharging time.
1. Fully discharge battery.
or
Ø
If the battery cannot be discharged: open separators on
the battery.
2. De-energize the connection cables to the DC link voltage.
3. De-energize the connection cables to the 24 V supply volt-
age.
4. Unscrew connection cables to the battery on the DC-DC
module.
5. Unplug connection cables for the DC link voltage on the DC-
DC module.
6. Unplug supply voltage 24 V DC.
7. Unplug data cable.
8. Unscrew protective earth.
6
‐
12
Dismantling
2020-07-01
A67-0140-00.BKen-0
01-05
WARNING
Removing residual voltages
Unscrew or unplug cables
Содержание TruConvert DC 1000 Series
Страница 1: ...Operator s manual TruConvert DC series 1000 TruConvert System Control TruConvert Modular...
Страница 2: ......
Страница 6: ...II Good to know 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 36: ...3 12 Technical data dependent on device variant overview 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 38: ...7 Ethernet 4 10 8 RS 485 4 11 4 2 Interfaces 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 40: ...Fig 4 3 4 4 Protective earth TruConvert DC series 1000 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 48: ...4 12 RS 485 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 54: ...5 6 CSA certification 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 106: ...16 State diagram State machine Fig 7 19 7 38 State diagram 2020 07 01 A67 0140 00 BKen 0 01 05...