The Refrigerant Report Group sequence is as follows:
Report Heading
Refrigerant Temp & Pressure Report
Press <Next> <Previous> to Continue
Evaporator and Condenser Refrigerant Pressure
Evap Rfgt Pressure:
XXX.X psig
Cond Rfgt Pressure:
XXX.X psig
Saturated Evaporator Temperature/Evaporator
Refrigerant Pressure
Saturated Evap Temp:
XXX.X f/c
Evap Rfgt Pressure:
XXX.X psig
Saturated Condenser Temperature/Condenser
Refrigerant Pressure
Saturated Cond Temp:
XXX.X F/C
Cond Rfgt Pressure:
XXX.X psig
Saturated Evap Temperature and Discharge Temperature
The Discharge Temp will be displayed only if the Discharge Sensor
Option is installed.
Sat Evap Rfgt Temp:
XXX.X F/C
Compressor Discharge Temp:
XXX.X F/C
Purge Operating Mode/Purge Status
The following screen shall be suppressed if the selected Purge
Control/Type is “Stand-Alone Purge”.
Purge Operating Mode:
[mode]
Purge Status:
[status]
Possible values of [mode] are: Auto, Stop, On and Adaptive.
Possible values of [status] are:
Idle
(Condensing Unit is Off)
Running
(Condensing Unit is On)
Pumpout
(Temperature initiated pumpout)
Service Pumpout
(Pumpout initiated by the service switch)
Running - Pumpout Inhibited by low
Temp
(Pumpout inhibited by low liquid temp)
Pumpout Maximum Rate Disabled
(Max. Pumpout Rate alarm disabled)
34
CVRC-M-1D
Refrigerant Report
Содержание CVRC-M-1D
Страница 50: ...50 CVRC M 1D Service Settings...
Страница 126: ...5068 5506 Rev A CVRC M 1D 126...