Purge Service Log Reset
Service Log:
Press <Enter > to Reset
Purge Pumpout Time: X,XXX Pumpout Min
Service Log:
Press <Enter > to Reset
Time Since Last Rst: X,XXX Cal Days
Resetting in either screen above will reset both pieces of data to Zero.
Purge Maximum Pumpout Rate
The following screen shall be suppressed if the selected Purge
Control/Type is “Stand-Alone Purge”.
Purge Max Pumpout Rate:
XX Min/24 Hrs
Press
<+> <- >
to Change Setting
Range of values is 1 to 100 minutes/24 hours in increments of 1
minute/24 hours. Factory default is 20 minutes/24 hours.
Purge Service Excessive Pumpout Override Timer
The following screen shall be suppressed if the selected Purge
Control/Type is “Stand-Alone Purge”.
Help Note:
sed to override the previous screen, for service wor .
Prg Disable Pumpout Alarm for:
XX Hrs
Press
<+> <- >
to Change Setting
Range of values is 1 to 72 hours in increments of 1 hour. Factory default
is 0 hours.
58
CVRC-M-1D
Field Startup