Note:
The following will be displayed in sequence based on options
installed and is informational only. Setpoints can’t be changed here.
ASHRAE Guideline 3 Reports
ASHRAE Guidline 3 Report
Press (Next) (Previous) To Continue
Time of Day/Refrigerant Type
Current Time/Date
HH:MM
Refrigerant Type:
[type]
Possible values for refrigerant type are:
R11,R123, R12, R134a, R22, R113, R114, R500 and R502.
Chiller Operating Mode
Operating Mode
Operating
Operating Mode
Active Chilled Water Setpoint/Chilled Water Setpoint
Source
Active Chilled Water Setpoint:
XXX.X F/C
[Settings Source] CWS:
XXX.X F/C
Settings source will be one of the following:
1) Front Panel
2) Tracer
3) External Source
Active Current Limit Setpt/Current Limit Setpt Source
Active Current Limit Setpoint:
XXX %
[Setpoint Source]:
XXX %
Settings source will be one of the following:
1) Front Panel
2) Tracer
3) External Source
4) Ice Building
Refrigerant Monitor
The following item will be displayed if the IPCRfgt Monitor option is
installed. Where (Y) can equal 123, 11, 22, 134a or 12.
Refrigerant Monitor:
XXXX PPM R - YYYY
CVRC-M-1D
27
Chiller Report