Time Permitted at Minimum Capacity
The following will be displayed only if the Minimum Capacity Timer
setpoint is enabled.
Time Permitted at Min Cap:
XXX Min
Press
<+> < - >
to Change Setting
Range of values is 1 to 480 minutes in increments of 1 minute. Factory
default is 30 minutes.
Local Atmospheric Pressure
Local Atmospheric Pressure:
X.XX f/c
Press
<+> < - >
to Change Setting
The Range of Settings shall be 10 to 16 PSIG in increments of 1 or 0.1
PSIG or kPa depending on the Service Setup Screen XXX or XXX.X. The
Factory Default is 14.7 PSIG.
Min. Delta Pressure Calibration
The following will be displayed only if programmable analog output is set
to “Refrig Diff Press”:
Min Delta Press Calib (2 VDC)
XXXX PSID / kPa
Press
<+> < - >
to Change Setting
The rage of values is 0 to 400 Psid (0-2758 kPa) in increments of 1
Psid/kPa.
Factory Default is 0 Psid (0kPa).
Max. Delta Pressure Calibration
The following will be displayed only if programmable analog output is set
to “Refrig Diff Press”:
Max Delta Press Calib (10 VDC)
XXXX PSID / kPa
Press
<+> < - >
to Change Setting
The rage of values is 1 to 400 Psid (7-2758 kPa) in increments of 1
Psid/kPa.
Factory Default is 30 Psid (207kPa).
IGV Stroke Time
The following will be displayed only if the Inlet Guide Vane Output is set
to Pulsed.
Inlet Guide Vane Stroke Time:
XXX Sec
Press
<+> < - >
to Change Setting
The range of values is 15 to 100 Seconds in increments of 1 Second.
Factory Default is 45 Seconds.