Phase Unbalance Limit Enable
The following is suppressed if FastPak starter type is set to “Stand Alone
- No Starter Module”.
Phase Unbalance Limit:
[d/e]
Press
<+> <- >
to Change Setting
Possible values of [d/e] are: Disable, Factory Default is Enable.
Help Note:
of motor is derated by resetting the active current limit.
There is a nondefeatable
for
seconds must trip point.
Momentary Power Loss Protection Enable
The following is suppressed if starter type is set to AFD or if FastPak
Starter type is set to “Stand Alone - No Starter Module”.
Momentary Power Loss Protection:
[d/e]
Press
<+> <->
to Change Setting
Possible values of [d/e] are: Disable, Factory Default is Enable
Help Note:
On every power down, the reset inhibit timer is reset to
seconds if the motor temperature is
and
minutes if the motor
temperature is
.
Enhanced Oil Temp Protection
This screen was added in CTV Upgrade V (11/4/96).
Enhanced oil temp Protection:
[d/e]
Press
<+> <->
to Change Setting
Possible values of [d/e] are: Disable, Factory Default is Enable
Oil Temp Setpoint
The following is suppressed if Enhanced Oil Protection is set to Enable.
Oil Temp Setpoint:
XXX.X F/C
Press
<+> <->
to Change Setting
Range of values is 100
°
F to 160
°
F (37.8 to 71.1
°
C) in increments of 1
to 0.1
°
F or
°
Cdepending on the Service Setup Screen XXX or XXX.X.
Factory default is 143.5
°
F (61.9
°
C).
Low Oil Temp Cutout
The following is suppressed if Enhanced Oil Protection is set to Enable.
Low Oil Temp Cutout:
XXX.X F/C
Press
<+> <->
to Change Setting
Range of values is 80 to 140
°
F (26.7 to 60.0
°
C) in increments of 1 or
0.1
°
F or
°
Cdepending on the Service Setup Group Screen XXX or
XXX,X. Factory Default is 95
°
F (35.0
°
C).
60
CVRC-M-1D
Field Startup