94
CVRC-M-1D
Diagnostics Menu
The second screen is:
Press (Next) to display operating mode
at time of last diagnostic
The third screen will be the chiller operating mode display that was
present at the time that the most recent diagnostic occurred.
If there are one or more diagnostics present, the following displays will
be inserted into the display sequence. Diagnostics will be listed in
order of occurrence from newest to oldest. Diagnostics will be
displayed on two screens. The two screens will vary slightly depending
on whether the diagnostic is active or historic.
The first active diagnostic screen will be:
[Sequence Number ]
[Diagnostic Number ]
[Next]
[Diagnostic type]
The sequence number will run from 1 through n (n<=20) and number
the diagnostics sequentially where the most recent diagnostic is
sequence number [01].
The possible replacements for “diagnostic” messages are:
Warning Only - Reset Not Red (Applies to all IFW diagnostics)
Unit Shutdown - Reset Red (Applies to all MMR diagnostics)
Unit Shutdown - Automatic Reset (Applies to all MAR diagnostics)
The second active diagnostic display screen will contain the diagnostic
sequence number, a time and date stamp, and a help message
suggesting possible service procedures. The second active diagnostic
display screen will be:
[SN]
Occurred at HH:MM xm Mon xx, YY xxxx
[Help Message]