LWT Control Derivative Gain (Kd) Setpt
LWT Derivative Gain Setpt:
XX.X %
Factory Default is 00.0%F & 00.0%/C
The range of values is 0 to 10.0 %/
°
F (0 to 18.0 %/
°
C) in increments of
0.1. The factory default is 00.0 %
°
F (0.0 %/
°
C).
Help Note:
ate of change. igher number gets to the new value faster.
IGV MA IMUM Travel Setpt
IGV MAXIMUM Travel Setpt:
XX,XXX Steps
Press
<+> <- >
to Change Setting
Range of values is 0 to 60,000 Steps in increments of 100 Steps. Factory
default is 50,000 Steps.
Note:
This is also known as the 90 degree vane setting.
Guide Vane Closed Travel Stop
Guide Vane Closed Travel Stop:
XX%
Press
<+> <- >
to Change Setting
Range of Values is 0 to 100 % in increments of 1%. Factory default is 0%.
AF Adjustable Speed Control Algorithm Enable
The following menu will be displayed only if the Starter Type is Adaptive
Frequency.
AF Adaptive Speed Control Algorithm:
[d/e]
Press
<+> <- >
to Change Setting
Possible values of [d/e] are: Disable, Enable, Factory Default is Enable.
AF Leaving Water Standard Deviation
The following menu will be displayed only if the Starter Type is Adaptive
Frequency.
AF Leaving Water Standard Deviation:
X.X
Press
<+> <- >
to Change Setting
Range of Values is 0.5 to 4.0 in increments of 0.1. Factory Default is 1.0.
AF Pressure Coefficient Constant
The following menu will be displayed only if the Starter Type is Adaptive
Frequency.
AF Pressure Coefficient Constant:
XXXX
Press
<+> <- >
to Change Setting
Range of Values is 0 to 2000 in increments of 1. Factory Default is 800.
CVRC-M-1D
63
Field Startup