Acceleration Timeout Action
The following is suppressed if starter type is set to “Stand Alone No Str
Module”.
Acceleration Time Out Action:
[Action]
Press <+> <-> To Change Setting
Possible values for action include: Transition, Factory default is Shutdown.
Shutdown will result in an MMR Diagnostic. Transition will result in an
IFW diagnostic.
Starter Type
Recommended “Action” Value
Undefined
Contact Factory
Variable Speed
Shutdown
Y-Delta
Transition
X-Line
Shutdown
Solid State
Shutdown
Auto-Transformer
Transition
Primary Reactor
Transition
AFDB
Shutdown
Solid State SMCDP
Shutdown
Motor Over Temperature Protection
Motor Temp Protection:
[input]
Press
<+> < - >
to Change Setting
Possible value of [input] are:
3 Winding Sensors
MTCSwitch
Factory default is 3 Winding Sensors
Motor Winding RTD Type
The following is suppressed if motor temp protection is set to “MTC
Switch”.
Motor Winding RTD Type
[Type]
Press <+> <-> To Change Setting
Possible values for type are: 100 Ohm at 32
°
F (0
°
C), Factory default is
75 Ohm at 75
°
F (24
°
C).
High Pressure Cutout Setting
High Pressure Cutout Setting
XXXX PSIG
Press <+> <-> To Change Setting
The range of values will be (-5) - 500 PSIG in increments of 1 PSIG from
-5 to 5 PSIG and 5 PSIG increments from 5 to 500 PSIG. Factory default
is 15 PSIG for a standard unit and 25 PSIG for an ASME unit.
6.8948 kPa = 1 psi.
Help Note:
This is the ressure imit lgorithm that will, in sequence,
Limit - Hold - Close
vane opening.
Limit Loading - Hold Loading - Close
orced nload
CVRC-M-1D
73