When the cooling requirement is satisfied, the FastPak™ panel originates
a shutdown signal. The inlet guide vanes are driven closed for 50 seconds,
and the unit enters an adjustable post lube period. The compressor motor
and condenser water pump starter are deenergized immediately, but the oil
pump continues to run during this post lube interval. The evaporator pump
will continue to run.
Once the post lube cycle is complete, the unit returns to the auto mode.
24
CVRC-M-1D
Operation - TCI Setup Settings
Sequence and Timing Functions