TCI Module Dip Switch Settings
The TCI modules require that their boards be configured per the following
dip switch settings.
Module
Switch SW1
Position
1
2
3
Tracer COM 3
Off
Off
Off
Tracer COM 4
Off
On
Off
IPCBuffer
Off
Off
On
Printer
Off
Off
On
TCI Printer Interface to Printer Setup
A dedicated serial printer such as Trane part number PTR0001 is recom-
mended.
Suggested Serial Communications
Settings for Printer Interface
Baud Rate
4800
Data Bits
8
Stop Bits
1
Parity
None
Hand Shaking
X on - - X off
Enter these settings in the FastPak™ Clear Language Display (CLD). Also
enter the same settings in the printer (typically dip switches, see printer
manual for details).
It is very important that the Serial Communication
setting on the CLD and the printer are exactly the same!
See Figure 1 for printer cable connections. The pin 6 - pin 20 connection
on the DB25 is required for Trane serial printer part number PTR 0001.
22
CVRC-M-1D
Operation - Chiller Control System
Figure 1 - Serial Printer Connections