Ice Building Enable
The following will be displayed only if ice building option is installed.
Ice Building
[d/e]
Press <+> <- > to Change Setting
Possible values of [d/e] are: Disable and Enable. Factory Default is
Disable.
Enable turns on Ice Building mode from the front panel.
Front Panel Ice Termination Setpoint
The following will be displayed only if ice building option is installed.
Panel Ice Termination Setpoint:
XXX.X F/C
Press <+> <- > to Change Setting
Range of values is 20 to 32.0 F (-6.7 to 0.0 C) in increments of 1 or 0.1 F
or Cdepending on the Service Setup Screen XXX or XXX.X. Factory
Default is 27.0 F (-2.8 C).
Ice to Normal Cooling Timer
The following will be displayed only if ice building option is installed. This
allows for a timed Idle/Stop period for (X) minutes when coming out of ice
before going into the cooling mode.
Ice To Normal Transition:
XX MIN
Press <+> <- > to Change Setting
Range of values is 0 to 10 minutes. Default is 5 minutes.
Chilled Water Setpoint Source
If the Tracer option is installed, the word “Default” will appear in front of
the setpoint source. If Tracer fails, it defaults back to Front Panel
Setpoint.
[Default] Chilled Water Setpoint Source:
[source]
Possible values of [source] are:
Front Panel is Factory Default.
External Source
Future 1
Future 2
If Tracer does not choose to write a setpoint then the “default” setpoint
source is used, e.g. Front panel.
CVRC-M-1D
47