CVRC-M-1D
Diagnostics Tables
Diagnostic Description
Diag Type
Diag Active
Modes
(Non-Active
Modes)
Cause
Help Message
Purge: Loss of Comm with Starter
IFW
All
The purge module lost communications with the Starter
Module for 15 contiguous seconds.
IFW to the chiller, MAR to the Purge.
Check IPC
Wiring/Connections
Purge: Loss of Comm with Stepper IFW
All
The purge module lost communications with the Stepper
(Scorpio) Module for 15 contiguous seconds.
IFW to the chiller, MAR to the Purge.
Check IPC
Wiring/Connections
Purge: Loss of Comm with Stepper
#1
IFW
All
The purge module lost communications with the Chiller
Module for 15 contiguous seconds.
IFW to the chiller, MAR to the Purge.
Check IPC
Wiring/Connections
Purge Misconfigured as Retrofit
IFW
All
The Purge module is configured as a Retrofit application
instead of a FastPak application. Chiller module remaps
Purge Retrofit only diagnostics to this diagnostic. Check
the Purge input 1 pins 5,6. Open = FastPak application,
Short = Retrofit application.
See Purge Operation and
Maintenance Manual
Purge Misconfigured as UCP2
IFW
All
The Purge module is configured as a UCP2 application
instead of a Retrofit application. Check the Purge input
1 pins 5,6. Open = UCP2 application, Short = Retrofit
application.
See Purge Operation and
Maintenance Manual
Refrigerant Monitor Memory Lost
IFW
All
Refrigerant Monitor lost battery backed-up RAM.
a. IFW to the chiller, MMR/MAR to the Refrigerant
Monitor.
See Refrigerant Monitor
IOM Manual
Refrigerant Monitor IR Source
IFW
All
Refrigerant Monitor infrared optical source failure.
a. IFW to the chiller, MAR to the Refrigerant Monitor.
Check IR Source Wiring
and Connections
Refrigerant Monitor Chopper
IFW
All
Refrigerant Monitor optical bench photo-interupter failure.
a. IFW to the chiller, MAR to the Refrigerant Monitor.
Check Chopper Wiring
and Connections
Refrigerant Monitor Temp Sensor
IFW
All
Refrigerant Monitor bench temperature sensor failure.
a. IFW to the chiller, MAR to the Refrigerant Monitor.
Check Sensor Wiring and
Connections
Refrigerant Monitor Bench Flow
Loss
IFW
All
Air flow loss to the Refrigerant Monitor optical bench.
a. IFW to the chiller, MMR/MAR to the Refrigerant
Monitor.
See Refrigerant Monitor
IOM Manual
Refrigerant Monitor Scanner Flow
Loss
IFW
All
Air flow loss to the Refrigerant Monitor scanner.
a. IFW to the chiller, MMR/MAR to the Refrigerant
Monitor.
See Refrigerant Monitor
IOM Manual
Refrigerant Monitor Out of Temp
Range
IFW
All
Out of temperature range for measuring refrigerant
concentration.
Check Bench Heater,
Wiring Connections
Refrigerant Monitor Refrige Level
too Low
IFW
All
The Refrigerant Monitor read less than or equal to -5 ppm
refrigerant concentration.
Recalibrate Refrigerant
Monitor
Refrigerant Monitor Fault
IFW
All
An undefined diagnostic detected by the Refrigerant
Monitor.
a. IFW to the chiller, MMR to the Refrigerant Monitor.
See Refrigerant Monitor
IOM Manual
Refrigerant Monitor Calibration
Error (This diagnostic is currently
ignored by UCP2).
IFW
All
The Refrigerant Monitor calibration failed.
a. IFW to the chiller, MMR to the Refrigerant Monitor.
See Refrigerant Monitor
IOM Manual
Refrigerant Monitor Aux. Input
Error
IFW
All
The Refrigerant Monitor auxiliary input is outside the 4-20
mA range.
Check Signal at Input
Refrigerant Monitor External Reset IFW
All
The Refrigerant Monitor external reset switch is stuck in
the “reset” state or the switch/jumper is missing.
See Refrigerant Monitor
IOM Manual