HGBP Timer Enable
The following screen will be displayed only if HGBP is installed.
HGBP Timer:
Status
Press <+> <-> to Change Setting
The choices for Status are: Enable (ROM Default), Disable, Unlimited
Time.
Maximum HGBP Time
The following will be displayed only if HGBP is installed and the HGBP
Timer is enabled.
Maximum HGBP Time:
XXX Min
Press <+> <-> to Change Setting
The range of values is 1 to 480 minutes in increments of 1 minute. The
factory default is 30 minutes.
Help Note:
Turns off the unit at the ma imum time, i.e.
minutes.
HGBP Vane Position
This screen will be suppressed when the HGBP option is not installed.
HGBP IGV Target:
XX %
Press <+> <-> to Change Setting
Range of Values is 0 to 30% in increments of 1%. Factory Default is
10%.
Help Note:
ith hot gas enabled, the hot gas control chec s the vane
position to be less than or equal to this number.
LWT Control Proportional Gain (KP) Setpt
LWT Proportional Gain Setpt:
XXX.X % FC
Factory Default is 10% F & 18.0%/C
The range of values is 0 to 100%
°
F (0 to 180%/
°
C) in increments of 0.1.
The factory default is 10.0%/
°
F (18%/
°
C).
Help Note:
oo s at how far from set point and how fast we move the
vanes. igher number is faster.
LWT Control Integral Gain (Ki) Setpt
LWT Integral Gain Setpt:
X.XXX
Factory Default is 0.110%/F & 0.198%/C
The range of values is 0 to 1%/
°
F (0 to 1.8%/
°
C) in increments of 0.001.
The factory default is 0.110 %/
°
F (0.198 %/
°
C).
Help Note:
oo s at error from set point. ow long we have been away
Time from set point. higher number means the faster we converge on
the set point.