AF Re-Optimization Factor
The following menu will be displayed only if the Starter Type is Adaptive
Frequency.
AF Re-Optimization Factor:
X.XX
Press
<+> < - >
to Change Setting
Range of Values is 0.03 to 1.00 in increments of 0.01. Factory Default is
0.30.
AF Re-Optimization Timer
The following menu will be displayed only if the Starter Type is Adaptive
Frequency.
AF Re-Optimization Timer:
X.XX Hrs.
Press
<+> < ->
to Change Setting
Range of Values is 1 to 255 in increments of 1. Factory Default is 24.
AF Boundary Pressure Coefficient Intercept
The following menu will be displayed only if the Starter Type is Adaptive
Frequency.
Range of values is 0.01 to 2.00 in increments of 0.01. Factory default is
0.40. This set-point is setable from this screen but also changes as the
Adjustable Frequency Control Algorithm runs. It is similar to a clock
setting where you set it and then it runs from there.
AF Boundary PCY - Intercept:
X.XX
Press
<+> < ->
to Change Setting
AF Boundary Pressure Coefficient Intercept Maximum
The following menu will be displayed only if the Starter Type is Adaptive
Frequency.
AF Boundary PCY - Intercept Maximum:
X.XX
Press
<+> < ->
to Change Setting
Range of values is 0.01 to 2.00 in increments of 0.01. Factory default is
2.00.
AF Pressure Error Deadband
The following menu will be displayed only if the Starter Type is Adaptive
Frequency.
AF Pressure Error Deadband:
X.XX
Press
<+> < ->
to Change Setting
Range of values is 0.001 to 1.000 increments of 0.001. Factory default is
0.030.