Maximum Acceleration Time #1
The following is suppressed if starter type is set to “Stand Alone No Str
Module”.
Max Accel Time Setpt #1:
XX Sec
Press <+> <-> To Change Setting
The range of values is 2 to 64 seconds.
Starter Type
Recommended Maximum
Acceleration Timer #1 Setting
Undefined
Contact Factory
Variable speed
20
Y-Delta
27 (Factory Default)
X-Line
6
Solid State
20
Auto-Transformer
16
Primary Reactor
11
AFDB
20
Solid State, SMCDP 20
Maximum Acceleration Time #2
The following is suppressed if starter type is set to “Stand Alone No Str
Module”.
Max Accel Time Setpt #2:
XX Sec
Press <+> <-> To Change Setting
The range of values is 191 to 254 seconds. Factory default is 228
seconds. For security purposes the second setting is the 8-bit, one’s
complement of the first setting above, or equals 255 minus Timer #1
Setting. Example: Setting #2 is 255 -27 = 228.
Heatsink Start Inhibit Temperature Setpoint
Heatsink Start Inhibit Temp:
xxx.x f/c
Press <+> <-> To Change Setting
The range of values shall be 100.0 to 200.0
°
F (37.8 to 93.3
°
C ) in
increments of .1
°
F/
°
C. Default shall be 100
°
F (93.3
°
C).
External Chilled Water Setpoint Option
External Chilled Wtr Setpt:
[Status]
Press <+> <-> To Change Setting
Possible values for status are: Installed, Factory default is Not Installed.
External Current Limit Setpoint Option
External Current Limit Setpt:
[Status]
Press <+> <-> To Change Setting
Possible values for status are: Installed, Factory default is Not Installed.
72
CVRC-M-1D
Machine Configuration