BAS-SVX45F-GB
9
Overview
Hardware Terminations
Tracer UC600 supports the following hardware terminations:
•
Temperature sensors (resistive and thermistor)
•
Linear inputs 0–20 mA, such as humidity sensors
•
Linear inputs 0–10 VDC, such as indoor air-quality sensors
•
Linear outputs 0-20 mA, such as variable frequency drives
•
Linear outputs 0–10 VDC, such as accuators for dampers and valves
•
Pulse outputs, such as electric heat or humidifier control
•
Binary outputs, such as fan start/stop
•
One 3-wire pressure transducer input
Table 2.
UC600 device connections
Input/Output type
Quantity
Types
Range
Notes
Universal input
8
Thermistor
10k
Ω
– Type II, 10k
Ω
–Type III,
2252
Ω
– Type II, 20k
Ω
– Type IV,
100k
Ω
Resistive (Setpoint)
100
Ω
– 1M
Ω
RTD
Balco™ (Ni-Fe), 1k
Ω
; 375 (Pt),
385 (Pt), 1k
Ω
Current
0–20 mA (linear)
Voltage
0–20 VDC (linear)
Binary
Dry contact
Pulse Width Accumulator
Minimum 20 ms, opened or closed
Universal Input/Analog
Output
Configure using any combination of analog or binary inputs/analog outputs
6
Thermistor
10k
Ω
– Type II, 10k
Ω
–Type III,
2252
Ω
– Type II, 20k
Ω
– Type IV,
100k
Ω
The UC600 provides 600 mA of DC power for 0–
20 mA inputs and/or outputs, and to power
expansion modules. See the power budget
“Power Budget Check in an Un-powered
Inputs
Resistive (setpoint)
100
Ω
–1M
Ω
RTD
Balco™ (Ni-Fe), 1k
Ω
; 375 (Pt),
385 (Pt), 1k
Ω
Current
0
–20 mA (linear)
Voltage
0–20 VDC (linear)
Binary
Dry contact
Pulse Width Accumulator
Minimum 20 ms, opened or closed
Outputs
Current
0–20 mA @16 V
Voltage
0–10 VDC @20 mA
Pulse
12.5ms to 1 second (12.5ms
resolution), 1 second to 60 seconds
(0.5 second resolution)
Binary output
4
Relay (form A) wet
24 VAC, 0.5A maximum
Ranges are given per contact.
Pressure input
1
3-wire
0–5 inwc.
Pressure input supplied with 5 VDC. Designed for
Kavlico™ pressure transducers.
Point total
19