Appendix A: Configuring Tracer UC600 for BACnet/IP
Disable HTTP Communications
HTTP is used for Tracer TU network connections and future UC600 BACnet/IP display options.
Tracer TU can also connect directly through the USB port, with a Tracer SC, or another Tracer UC600
on the IP network.
For added security, HTTP Port 80 should be disabled if other connection options are viable (see
). This will prevent others from accessing the Tracer UC600 with a Web browser or
other HTTP applications. HTTP Port 80 is disabled with the Tracer TU service tool as described in
“Configuring IP Information,” p. 79
Disable Tracer UC600 User Interface (TD7)
If direct Tracer TU network addressing is needed, then access to the user interface through a Web
browser should be disabled. (See
). This is done with the Tracer TU service tool as
“Configuring IP Information,” p. 79
.
Note:
At this time the Tracer TD7 display option is not available when connecting with the BACnet/
IP protocol. This option will be available in a future Tracer UC600 firmware upgrade.