78
BAS-SVX45F-GB
Appendix A: Configuring Tracer UC600 for BACnet/IP
Setting Up Tracer UC600 BACnet Communication With Tracer TU
The procedures in this section describe how to initially connect to Tracer TU through a USB cable,
and then make the necessary BACnet/IP configurations in the Protocol group box on the controller
settings screen. Upon completion, you can connect to Tracer TU and view Tracer UC600 using the
BACnet/IP protocol. For more configuration tasks, see
“Configuring Tracer UC600,” p. 46
.
Note:
Tracer TU V8.6 or higher must be installed on Tracer UC600 to enable BACnet/IP
communication. Tracer UC600 firmware must be at V5.0 or higher.
Perform the following tasks in the order in which they are shown.
•
Establish a direct connection to Tracer TU.
•
Configure IP information
•
Configure BACnet information
•
Return to the Tracer TU Startup Task Panel to connect using the BACnet/IP protocol (see
“Establishing a Network Connection with Tracer TU,” p. 79
Establishing a Direct Connection with Tracer TU
To establish a direction connection:
1.
Connect a USB cable between the technician PC and the USB service port of the Tracer UC600.
The Startup Task Panel dialog box appears.
2. Select the Direct Connection radio button (
3. Click Connect.
Figure 43. Establishing a direct connection