34
BAS-SVX45F-GB
Wiring Inputs and Outputs
Wiring Trane Zone Sensors
The table in
shows the terminations on a Trane zone sensor and a typical UC600
application.
1.
Connect the shield to a common terminal at the terminal board device.
Note:
Do Not use the shield as the common connection. For 3-wire applications, use a
3-conductor cable with shield and for 2-wire applications, use a 2-conductor cable with
separate shield.
2. Connect the zone sensor wires to any available input (UI, UIO) terminals; refer to table 7 as an
example.
3. Use the Tracer TU service tool to configure the analog input that references the corresponding
hardware termination.
Figure 14. Typical wiring, Trane zone sensors
AO
6
UI
14
AO
5
UI
13
AO
4
UI
12
AO
3
UI
11
AO
2
UI
10
AO1
UI
9
BO
4
BO
3
BO
2
BO
1
RELAYS
0.5 A MAX
IMC
1
IMC
P
1
UI
8
UI
7
UI
6
UI
5
UI
4
UI
3
UI
2
UI
1
IMC
+24
VDC
LINK
OUT
+24
VDC
+24
VDC
OUT
24
VAC
MBUS
OUT
24
VAC
XFMR
24
VAC
SERVICE TOOL
SERVICE
LINK
ACT
IMC
MBUS
LINK
RX
TX
UC
600
ADDRESS
0 1
2
3
45
6
7
8
9
x1
0 1
2
3
45
6
7
8
9
x10
0 1
2
3
45
6
7
8
9
x100
BO
4
BO
3
BO
2
BO
1
4
3
2
1
Table 10. Example zone sensor terminations
Zone Sensor
Termination
Zone Sensor
Output
UC600
Termination
Type
Range
1
Zone Temp
UI1
Thermistor
10k
Ω
2
Ground
n/a
n/a
3
Zone Temp
Setpoint
UI2
Resistive
200
Ω−
20k
Ω
4
Fan Mode
UI3
Resistive
200
Ω−
20k
Ω
Note:
Example hardware terminations. Any universal input or universal
input/analog output may be used for terminating zone temp, zone temp
setpoint, or fan mode.
Fan mode
Setpoint
Space