BAS-SVX45F-GB
13
Installation
This section describes how to install Tracer UC600 onto a DIN rail and set rotary switches.
Mounting and Removing the Tracer UC600 Controller
The Tracer UC600 controller should be properly mounted on a DIN rail.
To mount or remove the controller from the DIN rail, follow the illustrated instructions in
. If using a DIN rail from another manufacturer, follow the recommended
installation procedures that accompany it.
Important:
When mounting the controller in a control cabinet, provide adequate spacing
between modules to allow for ventilation and heat dissipation.
NOTICE:
Avoid Equipment Damage!
Do not use excessive force to install the controller on the DIN rail. Excessive force could
result in damage to the enclosure.
Figure 4.
Mounting the Tracer UC600
To mount the controller:
1.
Hook device over top of DIN rail.
2. Gently push on lower half of device in
the direction of arrow until the release
clip clicks into place.
Table 1.
DIN unit width measurements
Device
Device Width (mm)
DIN Unit Width
(1 unit = 18 mm)
Tracer SC system controller
143.6 mm
8
Tracer UC400 controller
143.6 mm
8
Tracer UC600 controller
215.9 mm
12
Tracer UC800 controller
71.6 mm
4
Tracer XM30 expansion module
53.6 mm
3
Tracer XM32 expansion module
71.6 mm
4
Tracer XM70 expansion module
215.9 mm
12
PM014 power supply module
107.6 mm
6
Tracer BACnet terminator
35.6 mm
2
DIN Unit Width
The following table provides DIN unit width measurements for Trane devices.