Configuring Tracer UC600 with Tracer TU
Configuring Tracer UC600 and Creating or Editing Points
Configuring Tracer UC600
Use the Tracer TU Controller Settings Utility to configure the Tracer UC600. This utility configures
date and time, units of measure, and protocol.
1.
Navigate to Utilities > Status > Controller Settings. The Controller Settings utility opens.
Note:
The content of this screen is based on the type of controller that is connected and the
system protocol used to communicate with the controller.
2. Click Date and Time
to set the preferred date and time formats and then click Send to Device.
Optional: If daylight saving time is observed in the region where the Tracer UC600 resides,
select the Use Daylight check box. Select dates and time from the drop-down lists that follow
(see
).
3. Click Controller Units and set the preferred units of measure and then click Send to Device.
4. Click Protocol to display a list of protocols that the Tracer UC600 uses to communicate with
other controllers. For BACnet protocol, specify the
Baud Rate, and then click Send to Device.
5. If the device ID must be set manually (typically for 3rd party integrations), click Protocol again
and select the Use Soft Set Device ID check box. Enter a device ID, click Save, and then cycle
the power.
To return to the rotary dial Device ID setting, click Remove Soft Set ID
,
click Save, and then cycle
the power to the controller for changes to take effect.
Figure 23. Configuring the date and time