E6582062
2. Installation and wiring
2-46
2
9
■
With frame size A1
VFAS3-2004P to 2022P, VFAS3-4004PC to 4037PC
1
Remove the front cover.
For how to remove, refer to [2. 2. 1].
2
Remove two screws for switching of grounding
capacitor.
The grounding capacitor is disconnected.
Mount the removed screws to the positions shown
in the figure on the right and tighten them.
3
To recover the shipping state, mount the two
screws for switching of grounding capacitor and
tighten them.
The grounding capacitor is connected and
grounded.
4
After switching, mount the front cover.
For how to mount, refer to [2. 2. 1].
Important
• For models with two switching screws, be sure to set both screws to the same side.
Screw
Screw
Grounding
Non-grounding