E6582062
6-11
6. [Advanced] How to use parameters
3
4
6
9
6. 2. 4
Selecting input signals of the optional terminals
[AI4] and [AI5]
<F148: Terminal AI4 input select>
<F149: Terminal AI5 input select>
■
Function
These parameters select an input signal for the optional terminals [AI4] and [AI5].
■
Parameter setting
Title
Parameter name
Adjustment range
Default setting
F148
Terminal AI4 input select
1: Voltage input (0-10 V)
2: Voltage input (-10 to +10 V)
3: Current input (0-20 mA)
4: PTC input
5: PT100 (2-wire) input
6: PT100 (3-wire) input
7: PT1000 (2-wire) input
8: PT1000 (3-wire) input
9: KTY84 input
1
F149
Terminal AI5 input select
1
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3].
1: Voltage input (0-10V)
2: Voltage input (-10 to +10V)
3: Current input (0-20mA)
4: PTC input
5: PT100(2-wire)input
0.0Hz
STOP
12:46
F148 : AI4 input select