6. [Advanced] How to use parameters
3
4
6
9
<F319: Regenerative over-flux upper limit> is enabled when <F305: Overvoltage limit operation> is
set to "2" or "3".
This parameter is used to adjust the maximum value of energy the motor consumes during
deceleration. Increase this value if overvoltage tripping occurs during deceleration.
<F626: Overvoltage limit operation level> also serves as the parameter to set the dynamic braking
level.
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
Overvoltage limit operation level
Output
frequency
Voltage in the
DC section
<F626: Overvoltage limit operation level>