E6582062
6. [Advanced] How to use parameters
6-42
4
4
6
9
<F256: Run sleep detection time>
<F259: Run sleep detection time at startup>
<F391: Sleep detection hysteresis>
<F392: Wakeup deviation>
<F393: Wakeup feedback>
■
Function
This function is used to automatically decelerate and stop the inverter in the following case: the
inverter continues to run at the frequency set with <LL: Lower limit frequency>, which has a low
workload, for the period specified in <F256: Run sleep detection time> for energy-saving, etc. (sleep
function).
The LCD screen displays "LStP" during sleep.
■
Parameter setting
■
Guideline for the setting
This function is used to automatically decelerate and stop the inverter when it continues to run at the
frequency set with <LL: Low limit frequency>.
Set a duration with <F256: Sleep detection time>.
6. 9
Automatic stop when run continues at the
lower limit frequency (sleep function)
Title
Parameter name
Adjustment range
Unit
Default setting
F256
Run sleep detection time
0.0: Disabled
0.1 - 600.0
s
0.0
F259
Run sleep detection time
at startup
0.0: Disabled
0.1 - 600.0
s
0.0
F391
Sleep detection
hysteresis
0.0 - UL
Hz
0.0
F392
Wakeup deviation
0.0 - UL
Hz
0.0
F393
Wakeup feedback
0.0 - UL
Hz
0.2
0.0Hz
STOP
13:10
F256 : Sleep detection time
Min: 0.0
Max: 600.0
X1000
X100
X10
X1
0.0
s
Run signal [F] or [R]
ON
OFF
Output frequency (Hz)
Time (s)
<F259>
<F259>
<F256>
<F256>
<LL>
<LL> + <F391>
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...