E6582062
5. [Fundamental operation] How to use parameters
5-36
4
5
9
5. 3. 3
Acceleration/deceleration time adjustment
automatically according to load
<AU1: Automatic Acc/Dec>
■
Function
This is a parameter that automatically adjusts the acceleration/deceleration time according to the
load condition to prevent an overcurrent trip during acceleration/deceleration.
■
Parameter setting
■
Selecting a setting value
1: Automatic Acc/Dec
The acceleration/deceleration time is adjusted automatically in the range in which the output current
does not exceed the rated current of the inverter. The adjustment range is 1/8 to 8 times as long as
the time set with <ACC: Acceleration time 1> and <dEC: Deceleration time 1>. If you set suitable
values for the average load with <ACC: Acceleration 1> and <
d
EC: Deceleration 1> in advance, it
will be easy to deal with load fluctuation.
2: Automatic Acc only
Only the acceleration time is adjusted automatically. The speed is decelerated according to the
setting of <dEC: Deceleration time 1>.
Title
Parameter name
Adjustment range
Default
setting
AU1
Automatic Acc/Dec
0: Disabled
1: Automatic Acc/Dec
2: Automatic Acc only
1
0.0Hz
STOP
15:23
AU1 : Automatic Acc/Dec
0: Disabled
1: Automatic Acc/Dec
2: Automatic Acc only
Basic parameter
Acceleration time
Acceleration/deceleration time -> decrease
Deceleration time
Time (s)
Output frequency (Hz)
0
Small load
Large load
Acceleration time
Acceleration/deceleration time -> increase
Deceleration time
Time (s)
Output frequency (Hz)
0
<FH>
<FH>
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...