E6582062
13. Trip information and measures
13-2
4
4
8
9
13
E-13
002D
Abnormal
speed error
1) When <Pt: V/f Pattern> = "0" to "9", an
over speed condition occurred.
Over speed condition:
In case F623
≠
0.0, F624
≠
0.0, the
condition which estimated frequency is
not inside of "output frequency -
<F624>" to "output fre
<F623>" continues <F622> times.
2) When <Pt: V/f Pattern> = "10" to "11",
over speed continued by PG failure,
etc.
Over speed condition:
In case F623
≠
0.0, F624
≠
0.0, the
condition which measured frequency is
not inside of "output frequency -
<F624>" to "output fre
<F623>" continues <F622> times.
3) Due to overvoltage limit operation, the
output frequency exceeded
<FH: Maximum frequency>
+12 Hz or <FH> + <vL: Base frequency
1> x 0.1.
1) 3)
• Check whether a problem exists in input
voltage.
• When the regenerative energy is large,
install a braking resistor (option).
2) Check the PG wiring and setting.
E-18
0032
Analog input
disconnecting
*
The input level of the terminal [II] became
the setting value or less of <F633: II
analog input disconnection detection
level>
• Check that the signal line connected to
the terminal [II] is not disconnected.
• Check if the <F633> setting is correct.
E-19
0033
CPU
communicatio
n error
Communication error between control
CPU.
Turn off the power and then turn it on
again.
If the error occurs again, contact your
Toshiba distributor.
E-20
0034
Over torque
boost
• The setting value of the <F402: Auto-
matic torque boost> is very high.
• Impedance on the motor is low.
Set the motor parameters according to the
motor characteristic, and perform auto-
tuning.
<vL: Base frequency 1>,
<vLv: Base frequency voltage>,
<F405: Motor rated capacity>,
<F415: Motor rated current>,
<F417: Motor rated speed>,
<F400: Offline auto-tuning>, etc.
E-21
0035
CPU1 fault B
Control CPU fault.
Fault in internal inverter.
Contact your Toshiba distributor.
E-22
0036
Embedded
Ethernet fault
Fault in the embedded Ethernet.
Fault in internal inverter.
Contact your Toshiba distributor.
E-23
0037
Option fault
(slot A)
Fault in the option connected to slot A.
Fault in the option.
Contact your Toshiba distributor.
E-24
0038
Option fault
(slot B)
Fault in the option connected to slot B.
Fault in the option.
Contact your Toshiba distributor.
E-25
0039
Option fault
(slot C)
Fault in option 3.
Fault in the option.
Contact your Toshiba distributor.
E-26
003A
CPU2 fault
Control CPU fault.
Fault in internal inverter.
Contact your Toshiba distributor.
*Enable/Disable can be selected for trip with a parameter.
Trip
display
Failure
code
Trip name
Detection factor
Measures
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...