E6582062
11-65
11. Table of parameters
1
3
9
10
11
118
119
STPC
Stop positioning
completion
ON: Stop position completion
120
121
LLS
During sleep
ON: During sleep
122
123
KEB
During synchronized Acc/
Dec
ON: During synchronized acceleration/deceleration
124
125
TVS
During traverse operation ON: During traverse operation
126
127
TVSD
During traverse Dec
ON: During traverse deceleration
128
129
LTA
Parts replacement alarm
ON: Any one of cooling fan, control board capacitor, or power
circuit capacitor reaches parts replacement time
130
131
POT
Overtorque (OT) pre-
alarm
ON: Torque current is 70% of <F616: Overtorque detection
level during power running> setting value or more
OFF: Torque current is under <F616> x 70%-<F619:
Overtorque detection hysteresis>
132
133
FMOD
Frequency command 1/
Frequency command 2
ON: <F207: Frequency command select 2> enabled
OFF: <FMOd: Frequency command select 1> enabled
134
135
FL3
Failure signal 3
ON: During trip (except Emergency off)
136
137
FLC
Hand/Auto
ON: Run command or panel run, OFF: Other than those at
left
138
139
FORCE
During forced run
ON: During forced run
140
141
FIRE
During fire speed run
ON: During fire speed run
142
143
UTA
Undertorque alarm
ON: Undertorque alarm level or more
144
145
PIDF
PID1,2 frequency
command agreement
ON: Frequency commanded by <F389: PID1 set value select >
and <F360: PID1 feedback input select > are within ± <F374:
PID1 set value agreement detection band>
150
151
PTCA
PTC input pre-alarm
ON: PTC thermal input value is 60% of <F646: PTC detection
resistance> or more
152
153
STO
During Safe Torque Off
(STO)
ON: Open between [STOA]-[STOB]-[PLC]
OFF: Short circuit between [STOA]-[STOB]-[PLC]
154
155
DISK
Analog input
disconnecting alarm
ON: The input value of terminal [II] is <F633: II analog input
disconnection detection level> or less
156
157
LI1
Terminal F ON/OFF
ON: Terminal [F] is ON, OFF: Terminal [F] is OFF
158
159
LI2
Terminal R ON/OFF
ON: Terminal [R] is ON, OFF: Terminal [R] is OFF
160
161
LTAF
Cooling fan replacement
alarm
ON: Cooling fan reaches parts replacement time
162
163
NSA
Number of starting alarm
ON: Number of starting is <F648: Number of starting alarm>
or more
164
165
LLD2
Light load detection 2
ON: Light load detection (compatible with old model)
166
167
DACC
During Acc
ON: During acceleration
168
169
DDEC
During Dec
ON: During deceleration
170
171
DRUN
During constant speed
run
ON: During constant speed run
172
173
DDC
During DC braking
ON: During DC braking
174
175
HSTOP
During hit and stop
ON: During hit and stop
176
177
SRVLR
During run including
servo lock
ON: During run including servo lock
Function Number
Symbol
Function
Action
Reference
Positive
logic
Negative
logic
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...