E6582062
6. [Advanced] How to use parameters
6-44
4
4
6
9
<F262: Panel jog run>
<F260: Jog frequency>
<F261: Jog stop select>
■
Function
Jog run represents inching the motor.
When you input a jog run signal, the inverter immediately outputs a jog run frequency regardless of
the set acceleration time.
You can start/stop jog run even on the operation panel.
■
Parameter setting
■
Setting example
Assign "18: jog run" to the unused input terminal.
While that input terminal is turned ON, the inverter can perform jog run.
To use only the panel jog run, you should not assign it to the input terminal.
Example) When it is assigned to the terminal [RES]: <F113: Terminal RES function 1> = "18"
The inverter outputs a low-speed detection signal but does not output an output frequency
attainment signal during jog run. Also, PID control is disabled.
<Example of jog run>
Terminal [RES] (JOG): ON + terminal [F]: Forward jog run when the terminal is turned ON
Terminal [RES] (JOG): ON + terminal [R]: Reverse jog run when the terminal is turned ON
(Frequency c terminal [F]: Forward run when the terminal is turned ON, terminal [R]:
Reverse run when the terminal is turned ON)
6. 10 Jog run
Title
Parameter name
Adjustment range
Unit
Default setting
F262
Panel jog run
0: Disabled
1: Enabled
0
F260
Jog frequency
F240 - 20.0
Hz
5.0
F261
Jog stop select
0: Deceleration stop
1: Coast stop
2: DC braking stop
0
0: Disabled
1: Enabled
0.0Hz
STOP
13:11
F262 : Panel jog operation
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...