E6582062
6-55
6. [Advanced] How to use parameters
3
4
6
9
■
Selecting the setting value
When using the regenerative power ride-through: <F302: Regenerative power ride-through> = "1"
• Set <F302> to "1: Regenerative power ride-through".
• A motor is controlled according to <F313: Ridethrough time>.
Note that the available time to continue the operation varies by the mechanical inertia or load
condition. The motor may enter the coasting state depending on the load condition.
• Set the operation level of regenerative power ride-through with <F629: Regenerative power ride-
through level>.
100% reference is 200 V (240V class), 400 V (480V class)
Set it to a value equal to <F625: Undervoltage detection level> decreased by 5%, or more. Or, set
it to a value equal to <F629: Regenerative power ridethrough level> increased by 5%, If the setting
is inappropriate, the regenerative power ride-through control time may become too short. This is
not required when <F625> is "80: Auto".
• When <F303: Retry> is used together, you can restart a motor without stopping it in case a trip
occurs.
• To restart a motor smoothly after restoration of power, use <F301: Auto-restart> together.
• This does not function during torque control.
When using the deceleration stop at power failure: <F302: Regenerative power ride-through> = "2"
• Set <F302> to "2: Deceleration stop at power failure".
• A motor makes a deceleration stop according to <F310: Dec time at power failure>. The
deceleration time is from <FH: Maximum frequency> to 0 Hz. With <F302> set to "2", <F310>
cannot be written during run.
• Set the operation level of deceleration stop at power failure with <F626: Overvoltage limit
operation level>. 100% reference is 200 V (240V class), 400 V (480V class).
• When the voltage falls to <F625: Undervoltage detection level> or less during a deceleration stop
due to power failure, the motor will enter the coasting state.
• "StOP" is displayed on the operation panel during the stop. The stop state is kept until the run
command is turned OFF.
• This does not function during torque control.
When using the synchronized Acc/Dec: <F302: Regenerative power ride-through> = "3" or "4"
• Set <F302> to "3: Synchronized Acc/Dec (TB)" or "4: Synchronized Acc/Dec (TB + power failure)".
• The deceleration time set by <F317: Synchronized stop time> and acceleration time set by <F318:
Synchronized reach time> are used.
• This does not function during torque control.
• The jog run is disabled while this function is set.
F313
Ridethrough time
0.0: Continuous
0.1 - 320.0
s
2.0
F317
Synchronized stop time
0.0 - 6000
s
2.0
F318
Synchronized reach time
0.0 - 6000
s
2.0
F625
Undervoltage detection
level
50 - 79
80: Auto
%
80
F629
Regenerative power
ridethrough level
55 - 100
%
75
Title
Parameter name
Adjustment range
Unit
Default setting
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...