E6582062
5-53
5. [Fundamental operation] How to use parameters
3
4
5
9
0: Frequency only
Only the frequency command is valid.
1: With function
For each preset speed commands of 1-speed to 15-speed, direction of rotation, acceleration/
deceleration time, V/f control, and torque limit can be set.
In this case, the direction of rotation of the motor is as set with <F561: Operation function (1-speed)>
to <F576: Operation function (0-speed)>, not as the input of terminal [F] or terminal [R].
Add the values of the functions to be used for setting. For example, when using the functions of Rev
run (+1) and Acc/Dec switching signal 1 (+2), set "3" (+1+2=+3).
Do not set +8, or +16 to F576.
Title
Parameter name
Adjustment range
Default setting
F560
Preset speed operation
style
0: Frequency only
1: With function
0
Title
Parameter name
Adjustment range
Default setting
F561 - F575
Operation function (1-
speed) to Operation
function (15-speed)
0: Fwd run
+1: Rev run
+2: Acc/Dec switching signal 1
+4: Acc/Dec switching signal 2
+8: V/f switching signal 1
+16: V/f switching signal 2
+32: Torque limit switching signal 1
+64: Torque limit switching signal 2
0
F576
Operation function (0-
speed)
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...