E6582062
6-157
6. [Advanced] How to use parameters
3
4
6
9
■
Guideline for the setting
The override functions calculate the frequency command value by means of the following
expression:
• Frequency command value × (1+<F661> Input (%)/100) + <F660> Input (Hz)
<F661> is limited to -100 to +100
However, when the setting value of <F661: Override multiplying input select> is *1 in the table, use
the following expression.
• Frequency command value × (<F661> Input (%)/100) + <F660> Input (Hz)
<F661> is not limited
■
Additive override
An input override frequency is added to the frequency command value externally.
Example 1: <F660>= "3: Terminal II", <F661>= "0: Disabled"
Output frequency = Reference fre Override (terminal [II] input (Hz))
Example 2: <F660>= "1: Terminal RR", <F661>= "0: Disabled"
Output frequency = Reference fre Override (terminal [RR] input (Hz))
■
Multiple override
An input override frequency is added to the frequency command value externally.
F729
Panel override
multiplication gain
-100 to +100
%
0
Title
Parameter name
Adjustment range
Unit
Default setting
Output frequency
Output frequency
Frequency after
override
Frequency after override
Fwd
Rev
Example 1: Terminal [RR]
(Reference frequency command)
Terminal
[II]
(override
input)
Example 2: Terminal [RX]
(Reference frequency command)
Terminal
[RR]
(override
input)
Override
([II] input)
Override
([II] input)
[RR] input
(Reference
frequency)
[RX] input
(Reference
frequency)
0
10V
10V
0
-10V
<FH>
<FH>
<FH>
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...