6. [Advanced] How to use parameters
6-188
4
4
6
9
6. 38. 2 Using RS485 communication
■
Operation by RS485 communication
To run/stop the inverter by RS485 communication, select "3: RS485 communication (connector 1)"
or "4: RS485 communication (connector 2)" with <CMOd: Run command select>.
To issue frequency commands by RS485 communication, select "21: RS485 communication
(connector 1)" or "22: RS485 communication (connector 2)" with <FMOd: Frequency command
select 1>.
Run commands and frequency commands by communication have priority over those from the
operation panel and terminals. Therefore, run commands and frequency commands from
communication can be enabled regardless of the settings of <CMOd> and <FMOd>.
However, when "48" (Communication priority cancel) of input terminal function selection is assigned
to the input terminal and a signal is input externally, perform panel run with the setting of <CMOd>
and <FMOd>.
When "2: Hand/Auto switching " is selected with <F750: EASY key function>, you can switch the
operation panel run and communication run with the [HAND/AUTO] key of the operation panel.
■
Transmission specifications
Item
Specifications
Communication
protocol
TOSHIBA inverter protocol
MODBUS-RTU protocol
Interface
RS485 compliant
Transmission scheme
Half duplex [Serial bus type (Line terminations resistor necessary at both ends of
system)]
Wiring
2-wire
Transmission distance
500 m max. (total length)
Connection terminals
32 max. (including upper host computer)
Inverters connected in the system: 32 max.
Synchronization
scheme
Start-stop synchronization
Communication baud
rate
9600 bps - 38.4 kbps
Character
transmission
ASCII mode: JIS X0201 8-bit (ASCII)
Binary mode: Binary codes fixed to 8 bits
Binary codes fixed to 8 bits
Error detecting
scheme 1
Parity: Even/Odd/Non parity (selectable using a parameter)
Error detecting
scheme 2
Checksum
CRC
Stop bit length
Received by inverter: 1bit/Sent by inverter: 2 bits
Order of bit
transmission format
Least significant bit transmitted first
Character
transmission format
11-bit characters (Stop bit =1, with parity)
Inverter Number
ASCII mode: 0 - 99
Binary mode: 0 - 63 (3Fh)
1 - 247
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...