E6582062
13. Trip information and measures
13-4
4
4
8
9
13
EEP1
0012
EEPROM
fault 1
Fault occurred during internal data writing. Turn off the power and then turn it on
again.
If the fault occurs again, contact your
Toshiba distributor.
EEP2
0013
EEPROM
fault 2
1) While setting <tyP: Default setting>, the
power was turned OFF or momentary
power failure occurred.
2) Fault occurred during internal data
writing.
1) Set <tyP> again.
If the fault occurs again, contact your
Toshiba distributor.
2) Turn off the power and then turn it on
again.
If the fault occurs again, contact your
Toshiba distributor.
EEP3
0014
EEPROM
fault 3
Fault occurred during internal data
reading.
Turn off the power and then turn it on
again.
If the fault occurs again, contact your
Toshiba distributor.
EF2
0022
Grounding
fault *
1) Grounding fault occurred in the output
wiring or the motor.
2) Fault can occur depends on motor, in
case of rapid acceleration/deceleration.
1) Check grounding fault in the wiring on
the output side and the motor.
2) Increase the acceleration/deceleration
time. <ACC/dEC acceleration/
deceleration time 1>
EPHI
0008
Input phase
loss *
1) Input side phase has failed.
1) Check phase failure in the wiring on the
input side.
EPHO
0009
Output phase
loss *
1) Output side phase has failed.
2) Output current is quite small (less than
8%) to motor rated current.
1) Check phase failure in the wiring on the
output side.
2) Set <F605> to 0
Err2
0015
RAM fault
Control RAM fault.
Fault in internal inverter.
Contact your Toshiba distributor.
Err3
0016
ROM fault
Control ROM fault.
Fault in internal inverter.
Contact your Toshiba distributor.
Err4
0017
CPU1 fault A
Control CPU fault.
Fault in internal inverter.
Contact your Toshiba distributor.
Err5
0018
Communication
time-out
(RS485)
RS485 communication timed out.
Check the communication equipment and
wiring on RS485 communication.
Err6
0019
Gate array
fault
Fault in the gate array.
Fault in internal inverter.
Contact your Toshiba distributor.
Err7
001A
Current
detector fault
Fault in the output current detector.
Fault in internal inverter.
Contact your Toshiba distributor.
Err8
001B
Communication
time-out
(option)
Communication option timed out.
Check the communication equipment and
wiring on communication option.
Err9
001C
Panel
disconnection
during run
While running with a run command from
the operation panel and extension panel,
the cable connecting the inverter and
panel are disconnected.
Check the connection on the inverter and
panel.
*Enable/Disable can be selected for trip with a parameter.
Trip
display
Failure
code
Trip name
Detection factor
Measures
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...