GTCOM2 User manual
47 |
E N
Figure 77Automation/ Sensors window
13.
Double click on the selected sensor’s line. Set other parameters of the sensor MIN, MAX values Units etc. Every field explanation:
14.
Write configuration to module, by pressing “Write” icon
Table 7 Explanation of every field in "Automation/ Sensors" window
26
X-multiplier=
Mult Coef Correction
X-
multiplier coefficient. Following the equation “Temperature=X*ADC+Y“to calculate X
and Y coefficients. Measure temperature in two points at least.
27
Y-offset=
Sum Coef Correction
Y-
offset coefficient. Following the equation “Temperature=X*ADC+Y“to calculate X and
Y coefficients. Measure temperature in two points at least.
Temperature= X*ADC+Y