EF200F-C
Commissioning
75
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Density calculation
The following conditions are
met:
• In the Select medium
parameter, the Gas option is
selected.
• In the Select gas type
parameter, the Natural gas
option is selected.
Select the norm the density
calculation is based on.
• AGA Nx19
• ISO 12213- 2
• ISO 12213- 3
AGA Nx19
Enthalpy type
The following conditions are
met:
• In the Select gas type
parameter, the User-
specific gas option is
selected.
Or
• In the Select liquid type
parameter, the User-
specific liquid option is
selected.
Define which kind of enthalpy
is used.
• Heat
• Calorific value
Heat
10.4.4 Configuring the current input
The "Current input" wizard guides the user systematically through all the parameters that
have to be set for configuring the current input.
Navigation
"Setup" menu → Current input