EF200F-C
Technical data
145
Description
Measured variable
Mass; 316L; 316L (integrated temperature measurement)
• Corrected volume flow
• Mass flow
• Calculated saturated steam pressure
• Energy flow
• Heat flow difference
• Specific volume
• Degrees of superheat
Order code for "Sensor version", option "mass flow (integrated temperature measurement)" combined
with order code for "Application package"
Description
Measured variable
Wet steam measurement
• Steam quality
• Total mass flow
• Condensate mass flow
Measuring range
The measuring range is dependent on the nominal diameter, the fluid and environmental
influences.
The following specified values are the largest possible flow measuring ranges (Q
min
to
Q
max
) for each nominal diameter. Depending on the fluid properties and
environmental influences, the measuring range may be subject to additional
restrictions. Additional restrictions apply to both the lower range value and the upper
range value.
Flow measuring ranges in SI units
DN
[mm]
Liquids
[m³/h]
Gas/steam
[m³/h]
15
0.076 to 4.9
0.39 to 25
25
0.23 to 15
1.2 to 130
40
0.57 to 37
2.9 to 310
50
0.96 to 62
4.9 to 820
80
2.2 to 140
11 to 1
800
100
3.7 to 240
19 to 3
200
150
8.5 to 540
43 to 7
300
200
15 to 950
75 to 13
000
250
23 to 1
500
120 to 20
000
300
33 to 2
100
170 to 28
000