Electrical connection
EF200F-C
48
•
•
•
•
Analog output: Temperature
Pulse output:
7.5 Connecting to TLV EC351 Flow Computer
This device can be used in combination with the flow indicator EC351. The correct-
ed flow rate of fluids whose temperature and pressure change (superheated steam,
air) can be displayed by combining with EC351 and a pressure sensor.
As for the connection with this device, the output and signal are associated as
follows as standard.
EF200F-C Settings
Assign pulse output 1: Pulse output: Mass flowrate (pulse output settings
→ See 10.4.6
(Current output settingas → See 10.4.5)
(pulse/frequency/switch output settings
→ See 10.4.6)
EC351 Settings
Function group: FLOW INPUT
Function: K-FACTOR
Selection: Set the specified values in the table below according to the size of the device.
Pulse width: 5 ms
Volume unit: L (litre) or dm3 (system units settings → See 10.4.2)
Value per pulse: Set the specified values in the table below according to the size of
the device.
Flowrate can be displayed on the EC351 without using the EF200-C analog output.
Connecting an external correction sensor to EC351 searately is necessary when displaying
the value converted to mass flow rate on the EC351.
Connection example when using analog output for data logger and displaying mass
flow rate on EC351
35
Power Supply
Data Receiver
(Analog 4 - 20 mA input)
Conpensation input signal
(pressure or temperature)
CAUTION
Size
0.0684
0.3478
0.8551
1.4258
3.1995
5.5420
12.6070
24.2000
38.1500
54.7200
Value per pulse
15
25
40
50
80
100
150
200
250
300
14.61988
2.87522
1.16945
0.70136
0.31255
0.18044
0.07932
0.04132
0.02621
0.01827
K-FACTOR
[P/I]
Size
15
25
40
50
80
100
150
200
250
300