Technical data
EF200F-C
152
Number of switching
cycles
Unlimited
Assignable functions
• Off
• On
• Diagnostic behavior
• Limit value
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
• Pressure
• Reynolds number
• Totalizer 1-3
• Status
• Status of low flow cut off
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure mode
Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
Pulse/frequency/switch output
Pulse output
Failure mode
No pulses
Frequency output
Failure mode
Choose from:
• Actual value
• 0 Hz
• Defined value: 0 to 1
250 Hz
Switch output
Failure mode
Choose from:
• Current status
• Open
• Closed