42
WARNING
The maximum operating pressure of this boiler
is 160 psig. Never exceed this pressure. This
boiler was supplied with a safety relief valve with
a pressure relief setting specified at the time of
purchase. The relief valve setting must be above
the maximum operating pressure of the system.
Consult Thermal Solutions if the desired system
operating pressure is above the safety relief
valve pressure setting. Do not plug or change
safety relief valve.
C.
Power the boiler
- Turn on electrical supply to the
boiler and circulation system at fused disconnect
switches. Note that there is electrical power at certain
components even with the power switch off. See wiring
diagrams in Figures 9a-9f.
D.
Power the Circulators
- Turn system circulators on
and purge air from the boiler and system piping.
1. Confirm motor rotation on boiler and system
circulators.
2. Confirm that water flow switch is operating properly.
E.
Pressurize the Fuel System
- Turn on gas supply to the
boiler gas piping.
1
.
Confirm that the supply pressure to the gas regulator
supplied with the boiler conforms to Table 2 for
maximum and minimum supply pressures.
2
.
Open the manual gas shut-off valves located
upstream of the gas regulator supplied with the
boiler. Do not open manual gas valve inside of boiler
jacket.
DANGER
Do not use matches, candles, open flames or
other ignition source to check for leaks.
3. Using soap solution, or similar non-combustible
solution, electronic leak detector or other approved
method, check that boiler gas piping valves,
regulators and all other components are leak free.
Eliminate any leaks.
4
.
Purge gas line of air.
5
.
Reset low gas pressure safety switch.
F.
Select Operational Mode
- Refer to the Thermal
Solutions Boiler Control
TM
(TSBC
TM
) Instruction
Manual to select the desired control features.
G.
Check Blower Rotation
- Remove air filter to expose
the fan blades.
1. Allow boiler to enter the sequence of operation.
2. While in Pre-Purge, position the flame control to the
test position.
3. Confirm proper blower motor rotation.
4. Shut boiler off and position the flame control back to
run. Reinstall air filter.
H.
Flame Safeguard Operation Check
- Turn boiler
operating switch to the ON position.
1. Allow boiler to complete prepurge and trial for
ignition period. Once pilot flame is recognized by
controller, position flame control switch to TEST
position.
2
.
Look through the boiler sight glass and confirm
that pilot flame is blue and steady and that the flame
signal is steady and between 1.5 and 5.0 volts DC.
On some boiler sizes, the pilot flame may not be
visible. In these cases, confirm proper flame signal
(as indicated above.)
3. Adjust pilot gas regulator until proper pilot manifold
gas pressure is achieved per firetest report label.
Pilot flame should be blue with very little yellow.
4
.
Turn the boiler off, place flame control switch in
"run" position, and repeat Steps H.1 and H.2 at least
five times until reliable pilot ignition and signal is
achieved and confirmed.
5
.
With the pilot operating properly, allow boiler to
continue to trial for main flame. Confirm that the
flame control locks out on main flame failure.
6
.
Open the manual main gas shut-off valve located
inside the boiler jacket. Using the procedure detailed
in Step E.3, leak test gas piping and valves inside of
jacket. Eliminate any leaks.
7
.
Reset flame safeguard and allow boiler to run
through prepurge, trial for pilot and trial for main
flame.
8. Confirm that main flame ignites smoothly.
9. Observe main flame and confirm that burner
element is evenly orange without flickering.
10. Observe flame signal and confirm signal is steady
and between 1.5 and 5.0 volts DC.
11. Using the procedure detailed in step E.3, leak test
gas piping and valves inside of jacket. Eliminate any
leaks.
12. Turn boiler off and repeat
Steps H.7-H.10 at least
five times to confirm proper main burner operation.
I.
Begin Commissioning the boiler
- With main flame
on, at high fire, measure gas pressure upstream and
downstream of the main gas valves
1. Adjust the manifold pressure to match the pressure
indicated on the factory firetest label.
2. Reassure that the inlet gas pressure is within the
acceptable range found in Table 2. Adjust if
necessary.
Содержание EVCA SERIES
Страница 13: ...13 Figure 3 Typical Sidewall Pressurized Venting Optional Figure 2 Typical Sidewall Pressurized Venting ...
Страница 14: ...14 Figure 4 Typical Vertical Pressurized Venting ...
Страница 16: ...16 Figure 6 Vertical Air Intake Piping Figure 5 Horizontal Air Intake Piping ...
Страница 19: ...19 Figure 8 Schematic Boiler Piping ...
Страница 25: ...25 Figure 9a 208 230 480V 1PH 3PH 60HZ Supply Power Wiring Schematic ...
Страница 26: ...26 Figure 9b 120V 1PH 60HZ Supply Power Wiring Schematic ...
Страница 27: ...27 Figure 9c Control Wiring Schematic EVCA 750 2000 ...
Страница 29: ...29 Figure 9e Control Wiring Schematic EVCA 3000 ...
Страница 32: ...32 Figure 10 Modular System Horizontal Air Intake Piping ...
Страница 33: ...33 Figure 11 Modular System Vertical Air Intake Piping ...
Страница 34: ...34 Figure 12 Modular System Typical One Pipe Water Piping ...
Страница 35: ...35 Figure 13 Modular System Typical Primary Secondary Water Piping ...
Страница 36: ...36 Figure 14 Modular System Typical Primary Secondary without System Pump ...
Страница 37: ...37 Figure 15 Modular System Typical Reverse Return Water Piping ...
Страница 38: ...38 Figure 16 Modular System Reverse Return with System Pump Only ...
Страница 39: ...39 Figure 17 Modular System Typical Primary Secondary with Reverse Return ...
Страница 55: ...55 Figure 18 Cleaning Secondary Heat Exchanger 1 2 ...
Страница 56: ...56 This page intentionally left blank ...
Страница 58: ...58 Figure 19 Boiler Combustion Chamber ...
Страница 60: ...60 Figure 20 Burner Assembly FRONT VIEW TOP VIEW ...
Страница 62: ...62 Figure 21a UL FM CSD 1 Main Gas Train Assembly EVCA 750 2000 ...
Страница 64: ...64 Figure 21b UL FM CSD 1 Main Gas Train Assembly EVCA 3000 ...
Страница 66: ...66 Figure 22a DB B Gas Train 750 Figure 22b DB B Gas Train 1000 2000 ...
Страница 68: ...68 Figure 22c DB B w POC Gas Train 750 Figure 22d DB B w POC Gas Train 1000 2000 ...
Страница 70: ...70 Figure 22e DB B Gas Train EVCA 3000 Figure 22f DB B w POC Gas Train EVCA 3000 ...
Страница 72: ...72 Figure 23 Jacket ...
Страница 74: ...74 Figure 24 EVCA 750 1000 and 1500 Secondary Heat Exchanger and Housing ...
Страница 78: ...78 Figure 25b EVCA 3000 Secondary Heat Exchanger and Housing ...
Страница 80: ...80 Figure 26 Control Panel Assembly ...
Страница 82: ...82 Figure 27 Bishop Pilot Assembly ...
Страница 97: ...97 NOTES ...
Страница 98: ...98 NOTES ...
Страница 99: ...99 NOTES ...