10
A.
VENTING
WARNING
Improper venting may result in property damage
and the release of flue gasses which contain
deadly carbon monoxide (CO) into the building,
which can cause severe personal injury and/or
death.
1. Venting Requirements
In order to properly vent this boiler, the installer
must select and install a vent system that meets all
requirements specified in this section (VENTING) as
well as following the instructions provided by the vent
system manufacturer.
a. The vent system shall be designed and constructed in
accordance with the National Fuel Gas Code/NFPA
54 ANSI Z223.1 and applicable local building codes to
develop a positive flow adequate to convey flue or vent
gasses to the outdoors.
b. If this boiler is being installed in Massachusetts, follow
the Massachusetts Code instructions printed later in this
section.
c. Consult the vent pipe manufacturer’s instructions for
vent system assembly and system specific installation
requirements.
WARNING
Vent pipe system must be made of materials
approved for use with condensing flue gasses.
d. Vent pipe system shall be acceptable for use with boiler
fuel type.
e. Vent pipe system shall be compatible either by directly
connecting, or by use of an adapter, to the boiler vent
connection.
i. This boiler is shipped with an AL 29-4C® Heat-Fab
Saf-T-Vent connection.
ii. Alteration of the boiler vent connection is
prohibited.
f. Do not reduce the diameter of the vent pipe. The vent
pipe must not be smaller than the vent connector on the
boiler.
g. Vent pipe system must be adequately supported at
intervals no less than five (5) feet apart. The completed
vent system must be rigid and able to withstand impacts
without collapse.
h. This boiler’s venting is Category IV (positive vent
pressure, flue condensing), with regards to National Fuel
Gas Code/NFPA 54 ANSI Z223.1.
i. Vent pipe system must be fully sealed.
j. Atmospheric venting is prohibited.
k. For multiple boiler installations, each boiler must have
its own independent vent system. Common venting
with additional or any other appliances is prohibited.
WARNING
Do not use vent dampers or barometric dampers
with this boiler.
l.
Direct vent applications:
For direct vent (ducted
combustion air) installations, the maximum vent length
is 50 equivalent feet. The vent length is equal to the total
length of straight pipe plus the equivalent length of vent
fittings.
m.
Non-direct vent applications:
For non-direct vent
installations (those without ducted combustion air),
design the vent system so that the pressure measured at
the outlet of the boiler is between 0”w.c. and 0.3”w.c. at
high fire.
n. If any point of the vent pipe system is higher than the
boiler flue collar, the vent system must have adequate
condensate drain loop(s) to prevent condensate from
running back into the boiler.
o. It is permissible to run vent pipe through a vertical
or horizontal chase provided minimum clearances to
combustible materials are maintained.
p. The minimum clearance to combustible material
is six (6) inches, unless otherwise specified by vent
manufacturer.
q. Horizontal vent pipe must slope no less than one (1)
inch in four (4) feet of run. For sidewall venting, slope
pipe toward vent termination if possible.
r. The vent termination location is restricted as follows:
i. Minimum twelve (12) inches above grade plus
normally expected snow accumulation or seven (7)
feet above grade if located adjacent to public walkways.
DO NOT INSTALL over public walkway where local
experience indicates condensation or vapor from the
boiler creates a nuisance or hazard.
III. Installation
Содержание EVCA SERIES
Страница 13: ...13 Figure 3 Typical Sidewall Pressurized Venting Optional Figure 2 Typical Sidewall Pressurized Venting ...
Страница 14: ...14 Figure 4 Typical Vertical Pressurized Venting ...
Страница 16: ...16 Figure 6 Vertical Air Intake Piping Figure 5 Horizontal Air Intake Piping ...
Страница 19: ...19 Figure 8 Schematic Boiler Piping ...
Страница 25: ...25 Figure 9a 208 230 480V 1PH 3PH 60HZ Supply Power Wiring Schematic ...
Страница 26: ...26 Figure 9b 120V 1PH 60HZ Supply Power Wiring Schematic ...
Страница 27: ...27 Figure 9c Control Wiring Schematic EVCA 750 2000 ...
Страница 29: ...29 Figure 9e Control Wiring Schematic EVCA 3000 ...
Страница 32: ...32 Figure 10 Modular System Horizontal Air Intake Piping ...
Страница 33: ...33 Figure 11 Modular System Vertical Air Intake Piping ...
Страница 34: ...34 Figure 12 Modular System Typical One Pipe Water Piping ...
Страница 35: ...35 Figure 13 Modular System Typical Primary Secondary Water Piping ...
Страница 36: ...36 Figure 14 Modular System Typical Primary Secondary without System Pump ...
Страница 37: ...37 Figure 15 Modular System Typical Reverse Return Water Piping ...
Страница 38: ...38 Figure 16 Modular System Reverse Return with System Pump Only ...
Страница 39: ...39 Figure 17 Modular System Typical Primary Secondary with Reverse Return ...
Страница 55: ...55 Figure 18 Cleaning Secondary Heat Exchanger 1 2 ...
Страница 56: ...56 This page intentionally left blank ...
Страница 58: ...58 Figure 19 Boiler Combustion Chamber ...
Страница 60: ...60 Figure 20 Burner Assembly FRONT VIEW TOP VIEW ...
Страница 62: ...62 Figure 21a UL FM CSD 1 Main Gas Train Assembly EVCA 750 2000 ...
Страница 64: ...64 Figure 21b UL FM CSD 1 Main Gas Train Assembly EVCA 3000 ...
Страница 66: ...66 Figure 22a DB B Gas Train 750 Figure 22b DB B Gas Train 1000 2000 ...
Страница 68: ...68 Figure 22c DB B w POC Gas Train 750 Figure 22d DB B w POC Gas Train 1000 2000 ...
Страница 70: ...70 Figure 22e DB B Gas Train EVCA 3000 Figure 22f DB B w POC Gas Train EVCA 3000 ...
Страница 72: ...72 Figure 23 Jacket ...
Страница 74: ...74 Figure 24 EVCA 750 1000 and 1500 Secondary Heat Exchanger and Housing ...
Страница 78: ...78 Figure 25b EVCA 3000 Secondary Heat Exchanger and Housing ...
Страница 80: ...80 Figure 26 Control Panel Assembly ...
Страница 82: ...82 Figure 27 Bishop Pilot Assembly ...
Страница 97: ...97 NOTES ...
Страница 98: ...98 NOTES ...
Страница 99: ...99 NOTES ...