Chapter 4 Software index
4-29
C30 =1, D is the deviation of (target value – feedback value) in the unit time (C34).
=2, D is the deviation of feedback value in the unit time (C34).
=3, D is the deviation of (target value – feedback value) in the unit time (C34). If the
deviation is positive, the output frequency decreases, vice versa.
= 4, D is the deviation of feedback value in unit time (C34).When the deviation is positive,
the frequency decreases, vice versa.
C31 Feedback gain : 0.00 - 10.0
C31 is feedback gain, that is feedback value = detected value × C31.
C32 P: Proportion gain : 0.00 - 10.0
C32: Proportion gain for P control.
C33 I: Integral time
(
s
)
: 00.0 - 100
C33: Integral time for I control
C34 D: Differential time
(
s
)
: 0.00 - 10.0
C34: Differential time for D control.
C35 PID offset 000: Positive direction
001: Negative direction
C36 PID offset adjust (%) : 000 ~ 109%
PID operation result can be adjusted by C36 (C35 effects the polarity of C36).
C30 PID operation mode
000: PID Function disabled.
001: PID Control, Deviation is derivative controlled
002: PID Control, Feedback id derivative controlled.
003: Same as 001 but (reverse characteristics control).
004: Same as 002 but (reverse characteristics control).
Содержание 7300EV
Страница 14: ...Chapter 3 Environment description and installation 3 4 z EV 1P2 1P5 101 2P2 2P5 201 N4S install TM1 TM2 ...
Страница 15: ...Chapter 3 Environment description and installation 3 5 z EV 1P2 1P5 101 2P2 2P5 201 N4 install TM1 TM2 ...
Страница 86: ...Chapter 6 Peripherals 6 4 z JNFS21015 22 07 FOR EV 202 203 H1 z JNFS21016 15 07 FOR EV 202 203 H3 ...
Страница 87: ...Chapter 6 Peripherals 6 5 z JNFS20858 7 07 FOR EV 401 403 H3 ...