Chapter 3 Environment description and installation
3-9
3.3.2 Suitable MC, MCCB, Fuse and wire specification.
MCCB/ MC/ Fuse
z
TECO warranty and replacement service will not apply under following condition.
(1)MCCB or fuse is not instal led or unsuitably installed or installed with over
capacity, which has resulted in inverter fault.
(2)MC or capacitor or surge absorber is connected in serries between inverter
and motor.
7300EV model
JNEV
□□□
H1(F)/H3 JNEV
□□□
H3(F)
1P2/2P2/1P5/2P5 101/201 202
203 401/402/403
Fuse
10A
300Vac
20A
300Vac
30A
300Vac
15A/600Vac
MCCB
Made by TECO
TO-50E
10A
TO-50E
20A
TO-50E
30A
TO-50E
15A
MC
Made by TECO
CN-11
CN-11
Main circuit terminal
(TM1/TM3)
Wire dimension
2.0mm
2
(14AWG)
Terminal screw
M4
Wire
dimension
3.5mm
2
(12AWG)
Terminal
screw
M4
Wire dimension
2.0mm
2
(14AWG)
Terminal screw
M4
Signal terminal
(TM2)
1~12
Wire dimension 0.75mm
2
(#18AWG)
,
Terminal screw M3
z
Use a single fuse for 1
ij
L/N inverter model, for 3
ij
models, each L1(L)/L2/L3(N) phase must
be fused..
z
Please select suitable three phase squirrel cage induction motor for inverter.
z
If a inverter drives multi motors, please pay attention to current in running should be
less than inverter nominal current. Suitable thermistor should be installed on each motor.
z
Please do not install capacitor, LC, RC between inverter and motor.
Содержание 7300EV
Страница 14: ...Chapter 3 Environment description and installation 3 4 z EV 1P2 1P5 101 2P2 2P5 201 N4S install TM1 TM2 ...
Страница 15: ...Chapter 3 Environment description and installation 3 5 z EV 1P2 1P5 101 2P2 2P5 201 N4 install TM1 TM2 ...
Страница 86: ...Chapter 6 Peripherals 6 4 z JNFS21015 22 07 FOR EV 202 203 H1 z JNFS21016 15 07 FOR EV 202 203 H3 ...
Страница 87: ...Chapter 6 Peripherals 6 5 z JNFS20858 7 07 FOR EV 401 403 H3 ...