Chapter 4 Software index
4-12
※
Note: C00=001, reverse command is disable.
F07 Frequency upper limit (Hz) : 01.0 - 200
F08 Frequency lower limit (Hz): 00.0 - 200
※
Note: If F07 = 0 Hz and frequency command = 0 Hz, the inverter will 0-speed stop.
If F08 > 0 Hz and frequency command
≦
F08, inverter output at F08 set value.
F09 Stopping method
000: Decelerate to stop
001: Free run ( Coast) to stop
1.) F09 = 000: after receiving stop command, the motor will decelerate to stop according to
setting of F02.
2.) F09 = 001: after receiving stop command, the motor will free-run (Coast) to stop.
F10 Status monitoring
display
000: Disable
001: Enable.
F10 = 001 displays motor current, voltage and DC link voltage, PID feedback.
Out put frequency
F07 (Frequency upper limit)
F08 (Frequency lower limit)
(
•••••
Comman
d Frequency