4-28
C16 VF base output voltage set
As C17=60HZ
C18=100%
If C16 setting 200~240V, then output voltage for the pattern:
When the output voltage is higher than the input voltage and the max. output voltage limit to the
max. input voltage.
C23 Torque Boost Gain (V/F) (%) 00.0 – 30.0%
C24 Slip Compensation Gain (V/F) (%) 00.0 – 100%
C25 Motor no load current
(
A
)
Motor no load current differs with inverter capacity F00. Please adjust it according the actual
condition.
C26 Electronic thermistor protection for motor (OL1) :
000: Protection Enabled
001: Protection Disabled
C27 Skip frequency 1 (Hz)
:
00.0 –200
C28 Skip frequency 2 (Hz)
:
00.0 –200
C29 Skip frequency range (± Hz)
:
00.0 –30.0
Example: When C27=10.0Hz/C28=20.0Hz / C29=02.0Hz
10Hz ±2Hz= 8-12Hz
20Hz ±2Hz=18-22Hz Skip frequency
C29
C28
C27
60.0Hz (C17)
C16=240
C16=220
C16=200
240
220
200