100949 Limit switch interprete
Description
The block evaluates limit switch signals. The edges of the limit switches and the
current directions of rotation are evaluated. This prevents a mixup of the limit
switches. A standstill behind the limit switch (e.g., due to ramps which are too flat)
is also reliably caught although the limit switch signal has already fallen again.
When the signals
LimSwiP
and
ActDirP
are active, the output
LSPCovrd
is set to
1:active
. When a falling edge of the signal
LimSwiP
is determined while the signal
ActDirN
is active, the output
LSPCovrd
is reset.
When the signals
LimSwiN
and
ActDirN
are active, the output
LSNCovrd
is set to
1:active
. When a falling edge of the signal
LimSwiN
is determined while the signal
ActDirP
is active, the output
LSNCovrd
is reset.
When the outputs
LSPCovrd
or
LSNCovrd
=
1:active
, the output
LimSAct
is
1:active
. EITHER a rising edge of the signal
LimSwiP
and an active signal
ActDirN
OR a rising edge of the signal
LimSwiN
and an active signal
ActDirP
sets the
output
LimFault
.
LimFault
is reset by
LimSAct
.
If the setting condition is true for the signal
LSPCovrd
or
LSNCovrd,
the output
LimEvent
is set.
LimEvent
is reset by one of the following conditions: Falling edge
of the signal
LimSwiP
or
LimSwiN,
LimFault
=
1:active
,
Reset
=
1:active
, or in case
of a malfunction
E48
= 5. The signal
LimRamp
corresponds to
LimFault
or
LimSAct.
Inputs
No. Name
Datatype Scaling
Description
1
LimSwiP
B –
Positive limit switch signal, display parameter
D303
2
LimSwiN
B –
Negative limit switch signal, display parameter
D304
3
ActDirP
B –
Positive
rotation direction signal
4
ActDirN
B
–
Negative rotation direction signal
5
Reset
B
–
External reset of the signal
LimEvent
Outputs
No. Name
Datatype Scaling
Description
6
LSPCovrd
B
–
Positive limit switch hidden
7
LSNCovrd
B
–
Negative limit switch hidden
8
LimSAct
B
–
Positive or negative limit switch hidden
9
LimRamp
B
–
Signal for decelerating ramp control
10
LimFault
B
–
Limit switches mixed up
11
LimEvent
B
–
Positive or negative limit switch has triggered.
Содержание POSIDRIVE MDS 5000
Страница 1: ...from V 5 6 D 02 2012 DE DESCRIPTION 5th generation of STÖBER inverters Blocks ...
Страница 12: ...Organization blocks Block descriptions ID 441692 01 www stoeber de 11 STÖBER ANTRIEBSTECHNIK ...
Страница 22: ...System blocks Block descriptions ID 441692 01 www stoeber de 21 STÖBER ANTRIEBSTECHNIK ...
Страница 322: ...Standard blocks Block descriptions ID 441692 01 www stoeber de 321 STÖBER ANTRIEBSTECHNIK ...
Страница 588: ...Notes Block descriptions ID 441692 01 www stoeber de STÖBER ANTRIEBSTECHNIK ...