System blocks
Block descriptions
ID 441692.01
STÖBER ANTRIEBSTECHNIK
216
256 R32->I16 (with saturation)
Description
The block converts values in data format R32 to format I16.
Input values which are less than -32768 are limited to -32768.
Input values which are greater than 32767 are limited to 32767.
NOTE
The conversion cuts off the positions after the decimal point of the floating-point representation.
Example: 123.5 is converted to 123.
Inputs
No. Name
Datatype Scaling
Description
1
In
R32 –
Input
value
Outputs
No. Name
Datatype Scaling
Description
2
Out
I16 –
Converted
value