Standard blocks
Block descriptions
ID 441692.01
STÖBER ANTRIEBSTECHNIK
527
100948 Range Control 1
Description
The block performs range control.
The value of the parameter entered in
D60
is read, multiplied by
D61
and filtered with
the time constant
D62
by a low pass. The result is written to
D69
and transferred to
range control.
Range control checks to determine in which of the five following ranges the value is
located and switches one of the five outputs to
1:active
. If the limits are correctly
specified (
D64
<
D65
<
D66
<
D67
), the following reactions occur.
D69
>
D67
is
1:active
D66
<
D69
≤
D67
is
1:active
D65
≤
D69
≤
D66
Ar1GRN
is
1:active
D64
≤
D69
<
D65
Ar1YEL-
is
1:active
D69
<
D64
Ar1RED-
is
1:active
The sequence of the check is shown by the numbering below. In particular this
specifies the reactions of the block when the inputs are not sorted as per
D64
<
D65
<
D66
<
D67
.
1
D69
>
D67
,
D194
is
1:active
2
D69
>
D66
,
D193
is
1:active
3
D69
<
D65
AreaRED-,
D192
is
1:active
4
D69
<
D64
AreaYEL-,
D191
is
1:active
5
Otherwise:
AreaGRN
,
D190
is
1:active
Parameter
D63
can be used to enable the creation of an absolute value.
Range control can be disabled by the signal on the input
Reset
.
Range control can also be disabled based on parameter
D68
. When
D68
is set to
0:inactive
, range control is disabled when
A900
=
0:inactive
or one of the signals on
AccActiv
or
DecActiv
is active. This can be used, for example, to disable range
control during accelerating or decelerating procedures. When
D68
is set to
1:active
,
range control is always calculated.
Inputs
No. Name
Datatype Scaling
Description
1
AccActiv
B
–
Signal for suppressing range control (e.g., acceleration active)
2
DecActiv
B
–
Signal for suppressing range control (e.g., deceleration active)
3
Reset
B
–
Direct signal for suppressing range control
Outputs
No. Name
Datatype Scaling
Description
4
B –
D69
>
D67
,
D194
=
1:active
and event 1 is triggered
5
B
–
D66 < D69
≤
D67, D193 = 1:active
6
Ar1GRN
B –
D65
≤
D69
≤
D66, D192 = 1:active
7
Ar1YEL-
B –
D64
≤
D69 < D65, D191 = 1:active
8
Ar1RED-
B –
D69 < D64
,
D190
=
1:active
and event 0 is triggered
Содержание POSIDRIVE MDS 5000
Страница 1: ...from V 5 6 D 02 2012 DE DESCRIPTION 5th generation of STÖBER inverters Blocks ...
Страница 12: ...Organization blocks Block descriptions ID 441692 01 www stoeber de 11 STÖBER ANTRIEBSTECHNIK ...
Страница 22: ...System blocks Block descriptions ID 441692 01 www stoeber de 21 STÖBER ANTRIEBSTECHNIK ...
Страница 322: ...Standard blocks Block descriptions ID 441692 01 www stoeber de 321 STÖBER ANTRIEBSTECHNIK ...
Страница 588: ...Notes Block descriptions ID 441692 01 www stoeber de STÖBER ANTRIEBSTECHNIK ...