Notice
If a country setting of Italy is set then the RS485 bus must be wired as follows in order to allow
control via an external device as per CEI 0-21.
–
External fast disconnection (Ital.: Teledistacco): If wires 3
1)
and 8
1)
of the RS485 bus
2)
are con-
nected, e. g. via an external relay, then the following applies:
Relay closes: The inverters connected to the bus disconnect themselves from the grid.
Relay opens: The inverters connected to the bus connect themselves from to the grid (normal
operation).
–
Switch-over of the grid frequency disconnection thresholds (ital.: Modalità definitiva di fun-
zionamento del sistema di protezione di interfaccia (impiego del SPI sulla base di letture locali
e di informazioni/comandi esterni)): If wires 5
1)
and 8
1)
of the RS485 bus
2)
are connected, e. g.
via an external relay, then the following applies:
Relay closes: The inverters connected to the bus set the switch-off thresholds as per CEI 0-21
to 47.5 Hz and 51.5 Hz.
Relay opens: The inverters connected to the bus set the switch-off thresholds as per the Italy
country setting; see the Technical Data section.
We recommend integrating the interconnection of wires 3, 5 and 8 into the bus termination.
1)
Pin assignments of the RJ45 plug for the RS485 bus: see Fig. 4.
2)
See
⑥
⑦
and
⑨
8
1
Fig. 4: Pin assignments (= wire number) of the RJ45 plug
One (!) of the following master devices can be connected to the RS485 bus. The devices support the
transfer protocol used by the inverter.
n
Energy management unit StecaGrid SEM: Interface to a ripple control receiver for EEG com-
pliant feed-in management
n
PC or notebook (with suitable software, for technical professionals only):
–
Load firmware updates
–
Read inverter information using Steca service software
–
An optional RS485
⇔
USB adapter for connecting to the inverter is also available from Steca.
n
External data loggers, recommended by Steca for professional system monitoring:
–
WEB‘log (Meteocontrol)
–
Solar-Log (Solare Datensysteme)
Notice
The correct settings must be made in external data loggers, according to the manufacturer's
instructions, before connecting them to the bus.
GB
747.431 | Z08 | 2014-01-31
99
Содержание coolcept StecaGrid 1800
Страница 76: ...DE 747 431 Z08 2014 01 31 76...
Страница 121: ...Entering system data 1 2 3 4 5 6 7 7 8 9 10 11 Fig 12 Data entry form for the system data GB 747 431 Z08 2014 01 31 121...
Страница 146: ...GB 747 431 Z08 2014 01 31 146...
Страница 147: ...1 Montage Installation Montage 148 2 Zertifikate Certificates Certificats 162 747 431 Z08 2013 12 10 147...
Страница 149: ...coolcept x 150 mm 240 mm 45 mm 210 mm 190 mm 320 mm 400 mm 748 339 Z01 747 431 Z08 2013 12 10 149...
Страница 162: ...2 Zertifikate Certificates Certificats 747 431 Z08 2013 12 10 162...
Страница 163: ...747 431 Z08 2013 12 10 163...
Страница 164: ...747431...